Product/Service

2'' Double Wall Handling Unit

Source: Buffalo Air Handling
2" Double Wall Handling Units have 14 or 16 gauge outer panels, 18 or 20 gauge inner panels (solid or perforated), 3#/ft³ density fiberglass insulation...
General Construction
• 2" double wall, 14 or 16 gauge outer panels, 18 or 20 gauge inner panels (solid or perforated), 3#/ft³ density fiberglass insulation.
• Galvanized steel, aluminum or stainless steel casings and floors
• Welded structural steel channel bases.
• 10 gauge or 3/16" welded floors in painted steel, galvanized, aluminum or stainless steel; treadplate optional.
• IAQ triple-sloped, 12 gauge, stainless steel drain pans in cooling coil sections for complete condensate removal.
• Access doors for inspection, service and maintenance designed to open opposite the unit operating pressure.
• Maximum 1% leakage rate.

Fan Section
• Fan, motor and drive are mounted on a welded heavy duty steel vibration base with spring isolators properly selected for the specified vibration efficiency. Inertia bases are available for critical applications.
• Complete fan assembly is factory run, tested and dynamically balanced not to exceed 0.16 ips horizontally and vertically, and 0.32 ips axially as measured by an Entek IRD computer balance analyzer.
• Centrifugal fans (DWDI) for maximum efficiency in return and supply fan applications.
• Plenum fans for return air applications and supply air applications with multiple discharges.
• Axial fans for reduced sound levels in the low octave bands.
• Direct drive available to meet critical balance criteria, and eliminate the possibility of belt dust and the necessity of belt maintenance.
• Full height, full width diffuser plate in blow through applications reduces pressure drop by 50% or more when compared to conventional diffusers.

Coil Section
• Chilled water and glycol cooling coils, hot water and glycol, and steam heating coils.
• IAQ triple-sloped, 12 gauge stainless steel drain pans in cooling coil sections.
• Support racks for independent coil removal available in stainless, galvanized or painted steel.
• Intermediate drain pans, troughs and downspouts for stacked coils.
• Steam coils raised for proper condensate removal.
• Preferred manufacturer is Aerofin.

Filter Section
• Flat and angle configurations.
• Upstream and side service options.
• ASHRAE rated, Carbon and HEPA filters

Dampers
• Opposed blade for maximum control.
• Parallel blade for mixing.

Louvers
• Drainable
• Acoustic

Buffalo Air Handling, 467 Zane Snead Drive, Amherst, VA 24521. Tel: 804-946-7455; Fax: 804-946-7941.